6.FOR
OPERATIONAL CHARACTERISTICS
FOR RESISTANCE
rp=
LmtpTp/ap
Where
=0.021 H mm2/m
d=mean diameter of primary
=265.825mm
Lmtp=length of mean
turns of primary=
d = 835.11mm
Now, rp=((0.021*835.11)/1.5393
)*2310 = 26.317 ohm
For secondary winding, rs=
LmtpTs/as
ds=mean diameter of LV =192.38mm
Lmts=
ds =
604.37mm
Total resistance refers to primary winding
Rp = rp + rs(Tp/Ts)2
= 26.317 +8.96*10-3(2310/50)2 = 45.44 ohm
PU resistance = (Ip*Rp)/ Vp
=(3.787*45.44)/11000 =
0.0156 ohm