Thursday, April 28, 2016

  2. DESIGN OF WINDOW
 We know, Q=3.33*f* m*Aw*kw* *10-3
For 125KVA transformer ,kw=10/(30+KV)
                                                    =10/(30+11)  =0.2439s
 Assuming the value of current density
 current density , = 2.3 N/mm2[for distribution transformer]
Aw= Q/(3.33*f* m*kw* *10-3)
      =125/(3.33*50*0.0226*2.3*103)
       =0.0577m2
Assume , window height to width ratio =3
           i.e  Hw/Ww=3
    where Hw=height of window
                Ww=width of window
Assuming window height to width ratio=3  Then, HW=3*Ww
        Now Aw= Hw*Ww
               Aw=3* Ww2
Ww= Aw/3)
Ww= (0.0577/3)
Ww=0.139
And Hw=3* Ww
               =3*0.139
               =0.417
Distance between adjacent limb(D)= Ww+d =0.139+0.174 =0.312m