2. DESIGN OF WINDOW
We know, Q=3.33*f*
m*Aw*kw*
*10-3
For 125KVA transformer ,kw=10/(30+KV)
=10/(30+11) =0.2439s
Assuming the value of current density
current density ,
= 2.3 N/mm2[for
distribution transformer]
Aw= Q/(3.33*f*
m*kw*
*10-3)
=125/(3.33*50*0.0226*2.3*103)
=0.0577m2
Assume , window height to width ratio =3
i.e Hw/Ww=3
where Hw=height of window
Ww=width of window
Assuming window height to width
ratio=3 Then,
HW=3*Ww
Now Aw= Hw*Ww
Aw=3* Ww2
Ww=
Aw/3)
Ww=
(0.0577/3)
And Hw=3* Ww
=3*0.139
=0.417
Distance
between adjacent limb(D)= Ww+d =0.139+0.174 =0.312m